Specifications
Initiating Device Circuits 10 Class B; Class A with optional N-CAC-5X converter module (2 required)
Notification Appliance Circuits (NACs)

2 Class B; Class A with optional N-CAC-5X converter module

each rated for 2.5 amps

Voice Evacuation Available Yes: requires direct connect to FireVoice 25/50
Power 7.0 amps total system power
Annunciators

Yes; up to 8 LCD type

Printer Interface Yes: serial or parallel
DACT (Digital Alarm Communicator/Transmitter) Yes; Built-in
Display 80-character LCD